Free tool

Watts to Amps Calculator

Divide watts by volts and you have a current. Divide by power factor as well and you have the current the conductor actually carries — and then the circuit that current requires, which is the part most conversions stop short of.

Watts ÷ volts, then two things most converters leave out

amps = watts ÷ volts on a DC circuit; watts ÷ (volts × power factor) on single-phase AC; and watts ÷ (volts × √3 × power factor) on three-phase AC.

The two omissions that matter: power factor, without which a motor circuit is under-reported by 15 to 20 percent, and the 125 percent continuous-load factor in NEC 210.19(A)(1) and 210.20(A), which is what turns a current into a breaker size. This tool carries both through to the smallest standard rating in NEC 240.6(A) — and declines to name a wire size, because the inputs for that are not on this page.

The load

The nameplate figure, in W. Enter 1.5 kW as 1500.

The circuit voltage — 120, 240, 277, or the DC system voltage.

System

Use the nameplate value where the equipment states one. A power factor below 1 means the conductor carries more current than the wattage alone suggests.

The answer

Current draw

12.50 A

amps = watts ÷ (volts × power factor)  →  1,500 W ÷ (120 V)

What the circuit has to be

Design current (load is not continuous)12.50 A
Smallest standard overcurrent device, NEC 240.6(A)15 A
Load a 15 A device may carry continuously (80% of its rating)12.00 A

No continuous-load factor has been applied. If the maximum current will in fact run for three hours or more, tick the box — it is the difference between a 15 A device and the next size up on many loads.

What this does not tell you

A conductor size. Ampacity depends on the conductor material, the insulation temperature rating, the terminal rating, how many current-carrying conductors share the raceway and the ambient temperature — none of which are entered here. The overcurrent device above is the starting point for that calculation, not a substitute for it.

Motor circuits are sized differently. Branch-circuit conductors and protection for a motor are taken from the tables in NEC Article 430 using the full-load current for the motor, not from the nameplate wattage. Use this figure to sanity-check a motor load, not to size its circuit.

Informational use only, please verify before you rely on it

This reproduces standard electrical conversion arithmetic together with the continuous-load provisions in NEC 210.19(A)(1) and 210.20(A) and the standard ampere ratings in NEC 240.6(A), reported across the residential range to 200 A. It is a preparation aid, not a determination and not a design. It does not size conductors, which requires the conductor material, insulation and terminal temperature ratings, raceway fill and ambient temperature. Motor branch circuits are governed by NEC Article 430 and are not sized from nameplate wattage. Jurisdictions adopt different NEC editions and amend them, and equipment listings and instructions govern. Confirm with the authority having jurisdiction and have electrical work performed by a licensed electrician.

This tool is provided for general informational and educational purposes only. Its output is an illustrative estimate generated from the values you enter and from general assumptions that will not match every deal, market, lender, or homeowner. It is not tax, legal, accounting, financial, or professional advice, and it is not a quote, an offer, a credit decision, or a guarantee of pricing, approval, timing, savings, or eligibility.

You are solely responsible for independently confirming all information presented here including any figures, rates, fees, margins, timelines, tax treatment, and federal, state, local, or utility incentives, with the applicable lender, authority having jurisdiction, and your own qualified tax, legal, and financial advisors before acting on it, relying on it, or presenting it to a homeowner or any third party. Incentive programs, lender terms, and permitting requirements change frequently and vary by jurisdiction.

Seamless Home is not a tax advisor, law firm, lender, or licensed installing contractor, and makes no representation or warranty as to the accuracy, completeness, or currency of the information produced by this tool. To the fullest extent permitted by law, Seamless Home accepts no liability for any decision made or action taken in reliance on it.

Where the conversion stops being arithmetic

A wattage-to-current conversion is usually the first step in a question about whether an existing panel can take one more thing. That second question has a different shape: it is about the busbar and the main breaker rather than the load. The NEC 120 percent rule sets out how backfed solar is added to a panel without exceeding the busbar rating, and the backfeed capacity calculator works that limit directly.

For a battery, the running total matters more than any single conversion. The critical load panel planner sums the circuits you want backed up against an inverter's continuous rating and tests the largest motor starting while the rest of the house runs — which is the case a per-load conversion cannot see, because it is about several loads at once. What a critical load panel is covers why that subpanel exists at all.

Working clearance is the requirement that most often turns a straightforward equipment addition into a relocation: how much working clearance solar equipment needs covers the space that has to stay empty in front of anything likely to be serviced energised. For the panel, service and equipment work itself, see home battery and backup power.

Frequently Asked Questions

How do you convert watts to amps?+

Divide watts by volts. On a DC circuit that is the whole calculation: a 1,200 W load at 12 V draws 100 A. On an AC circuit you divide by the power factor as well, because watts measures only the part of the power doing work. On a three-phase AC circuit you divide by the square root of three (about 1.732) in addition to the voltage and the power factor. The tool applies whichever of the three formulas matches the system you select, and shows the arithmetic it used.

Why does power factor change the answer?+

Because a conductor carries current, not watts. On an AC circuit with an inductive load — a motor, a compressor, an air handler — current and voltage fall out of step, so some of the current flowing does no useful work. Watts counts only the useful part. The quantity the conductor and the breaker actually see is apparent power, measured in volt-amperes, and it equals watts divided by power factor. A 1,000 W motor at 0.85 power factor draws the same current as a 1,176 VA resistive load, which is why a wattage-only conversion under-reports a motor circuit by roughly 18 percent.

What is a continuous load, and why does it add 25 percent?+

A continuous load is one where the maximum current is expected to continue for three hours or more. NEC 210.19(A)(1) requires the branch-circuit conductor to have an ampacity of not less than 125 percent of that load, and 210.20(A) requires the overcurrent device to be rated not less than 125 percent of it. The factor exists because overcurrent devices are thermal devices calibrated in open air, and a breaker sitting in a loaded panel for hours behaves differently from one tested on a bench. EV charging, PV output, electric heat and a water heater recovering from cold are the common residential cases.

Why is the breaker bigger than the calculated current?+

Because standard overcurrent devices only come in the ratings listed in NEC 240.6(A) — 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 and upward — so the design current is rounded up to the smallest standard rating that is not less than it. The tool also reports the same relationship from the other direction: a device may carry 80 percent of its rating continuously, which is the arithmetic inverse of the 125 percent factor. If the load you entered is above that figure, the circuit is undersized even though the breaker will hold.

Can this tool tell me what wire size to use?+

No, and it deliberately does not try. Conductor ampacity depends on the conductor material, the insulation temperature rating, the rating of the terminals at both ends, how many current-carrying conductors share the raceway and the ambient temperature — none of which this tool asks for. Reporting a wire gauge from a wattage and a voltage alone would be a figure that looks authoritative and is not. The overcurrent device shown here is the starting point for that calculation, not a replacement for it.

Does this work for motor circuits?+

Use it to sanity-check a motor, not to size its circuit. Branch-circuit conductors and short-circuit protection for a motor are taken from the tables in NEC Article 430, using the full-load current values in those tables rather than the motor's nameplate wattage, and the permitted overcurrent device can be far larger than the running current because it has to let the motor start. A conversion from nameplate watts will give you an approximate running current and will not give you a compliant motor branch circuit.

Is this a determination?+

No. It reproduces the conversion arithmetic and the continuous-load and standard-rating provisions of the NEC as a preparation aid. Jurisdictions adopt different NEC editions and amend them, the equipment's own listing and instructions govern, and the 125 percent factor does not apply where the assembly containing the overcurrent device is listed for operation at 100 percent of its rating. Confirm against the edition your building department has adopted.

Get the circuit specified before the equipment arrives

Seamless Home owns the design and permit layer on the work it runs, which is where a load calculation stops being an estimate and becomes a documented one an inspector can follow. Coverage is confirmed per service area rather than promised as blanket availability.

Get a Free Estimate