Volts need a second figure

watts = volts × amps — times the power factor on AC, and times 1.732 as well on three-phase. 120 V at 15 A is 1,800 W; 12 V at 10 A is 120 W. From a heating element's resistance, watts = volts² ÷ ohms.

Volts alone never convert: the same outlet runs a phone charger and a space heater. The case people actually meet is the 240 V appliance on 208 V, common in apartments — a resistive element delivers about 75 percent of its rating, because power in a fixed resistance goes with the square of voltage.

What you know besides the volts

12, 24, 48, 120, 240…

What the load draws, not the breaker size.

Use the nameplate if it states one. 1.00 for a heater; about 0.85 for a motor.

The answer

Real power

1,800 W

120 V × 15.00 A × 1.00 PF

What this does not tell you

Whether a circuit can carry the load. A breaker rating is not a load, and the limits on what a circuit may run — 80 percent for a continuous load, and the NEC 210.23 limits on shared circuits — are a separate question. Nor does it name a wire size.

Informational use only, please verify before you rely on it

This reproduces standard conversion arithmetic between voltage, current, resistance and power for DC, single-phase and three-phase circuits. It is a preparation aid, not a determination. The re-rating calculation is valid only for resistive loads. It does not assess whether a circuit, conductor or overcurrent device can carry the result, and does not name a conductor size. Confirm against the equipment nameplate and installation instructions and with the authority having jurisdiction.

This tool is provided for general informational and educational purposes only. Its output is an illustrative estimate generated from the values you enter and from general assumptions that will not match every deal, market, lender, or homeowner. It is not tax, legal, accounting, financial, or professional advice, and it is not a quote, an offer, a credit decision, or a guarantee of pricing, approval, timing, savings, or eligibility.

You are solely responsible for independently confirming all information presented here including any figures, rates, fees, margins, timelines, tax treatment, and federal, state, local, or utility incentives, with the applicable lender, authority having jurisdiction, and your own qualified tax, legal, and financial advisors before acting on it, relying on it, or presenting it to a homeowner or any third party. Incentive programs, lender terms, and permitting requirements change frequently and vary by jurisdiction.

Seamless Home is not a tax advisor, law firm, lender, or licensed installing contractor, and makes no representation or warranty as to the accuracy, completeness, or currency of the information produced by this tool. To the fullest extent permitted by law, Seamless Home accepts no liability for any decision made or action taken in reliance on it.

Why the question is usually about 208 volts

A detached house has 120/240 V. Many apartment and condominium buildings take a three-phase 208Y/120 V service instead, and each unit is fed two of the phases, which are 208 V apart rather than 240. Single-phase vs three-phase power explains how to tell which a building has from the panel label. Outlets are unaffected; the water heater, baseboard heat and range are not, and that is where a volts-to-watts conversion starts to matter.

For a load that is not a heater, the watts depend on power factor as much as on voltage. What power factor is covers why a motor's volt-amps and watts differ, and how many amps a refrigerator uses works an example through from the rating label. To go the other way, the watts to amps calculator carries a load through to the circuit it needs.

Frequently Asked Questions

How do you convert volts to watts?+

You cannot from volts alone — a voltage is a pressure, not an amount of power, and the same 120 V outlet can supply a 5 W phone charger or a 1,800 W space heater. You need a second figure. With the current: watts = volts × amps, so 120 V at 15 A is 1,800 W and 12 V at 10 A is 120 W. With the resistance of a heating element: watts = volts² ÷ ohms, so a 12.8 ohm element at 240 V dissipates 4,500 W.

Does power factor change the answer?+

On AC, yes, for anything that is not a plain resistance. Volts times amps gives volt-amperes, the apparent power the wiring carries. The watts — the power doing work — are volt-amperes times the power factor. A heater has a power factor of 1, so the two are equal. A motor under load is typically around 0.85, so a compressor drawing 5 A at 120 V is 600 VA but about 510 W. On DC there is no power factor.

How many watts is a 240 V appliance on 208 V?+

For a resistive appliance — a water heater element, baseboard heater, range or dryer element — about 75 percent of its rating. Its resistance is fixed, so power goes with the square of the voltage: (208 ÷ 240)² is 0.751, and a 4,500 W element delivers about 3,380 W. This is the ordinary case in an apartment on a 208Y/120 V building service. It does not apply to equipment that controls its own current, such as an EV charger, which loses about 13 percent.

What about three-phase?+

Multiply by the square root of three, about 1.732, as well, using the line-to-line voltage: watts = volts × amps × 1.732 × power factor. 20 A per line at 480 V and a power factor of 0.9 is about 14,965 W. Entering the line-to-neutral voltage — 120 on a 208Y/120 system or 277 on 480Y/277 — understates the power by the same 1.732, and the tool flags both.

Can I use a breaker rating as the amps?+

Only to find the ceiling, not what anything draws. 15 A at 120 V is 1,800 W, which is the most the breaker allows before it trips, not a load the circuit may carry for hours. A continuous load is limited to 80 percent of the rating, and the NEC 210.23 limits on a shared circuit are lower still for one appliance. The amps to watts calculator works through those limits from a breaker rating.

Is a higher voltage more powerful?+

Not by itself. A higher voltage delivers the same power at less current — a 4,800 W load draws 40 A at 120 V and 20 A at 240 V — which is why large appliances run on 240 V: the smaller current needs smaller conductors. What decides the power is the load. The exception is a fixed resistance, where raising the voltage does raise the power, with the square of the change, and supplying it above its rating overdrives it.

Is this a determination?+

No. It reproduces the standard conversion arithmetic as a preparation aid. It does not assess whether a circuit, conductor or breaker can carry the result, and the re-rating arithmetic is valid only for resistive loads. Confirm figures against the equipment nameplate and installation instructions, and with the authority having jurisdiction.

Get the load worked out before the equipment arrives

Seamless Home owns the design and permit layer on the work it runs, which is where a service voltage and a load are confirmed rather than assumed. Coverage is confirmed per service area rather than promised as blanket availability.

Get a Free Estimate